    제목(국문) 이중 윅 타입 히트파이프를 이용한 바닥복사패널의 난방특성 연구
    제목(영문) A Study on the Heating Characteristics of Radiant Floor Panel Using Heat Pipes with the Double Wick
    저자 김용기 (Yong-Ki Kim ,한국건설기술연구원 화재 및 설비연구부 ) ▷공저자네트워크등록하기
    이태원 (Tae-Won Lee ,한국건설기술연구원 화재 및 설비연구부 ) ▷공저자네트워크등록하기
    초록

    Most of the domestic residential buildings have nsed the traditional radiant heating system, circulating hot water through the cross-linked polyethylene(PE-X) pipe buried in the floor panel of the heating space. New type of the heating panel was recently developed using heat pipes with double wicks. Some experiments were carried out in this study to verify the thermal characteristics of this heating system at the unit heating space which surrounded by outer space whose temperature of air be maintained scheduled value with time. Through the various experiments with several parameters, such as flow rate, inlet and outlet temperatures of hot water and the heating duration and so on, we found that the floor heating system with heat pipes was able to reduce
    the pumping power for hot water circulation by 4-31% compared with the conventional panel heating system using PE~X pipe. These results could be used for optimal design and efficient operation of the heating system as well as improvement of thennal comfort.

    초록(영문)

    Most of the domestic residential buildings have nsed the traditional radiant heating system, circulating hot water through the cross-linked polyethylene(PE-X) pipe buried in the floor panel of the heating space. New type of the heating panel was recently developed using heat pipes with double wicks. Some experiments were carried out in this study to verify the thermal characteristics of this heating system at the unit heating space which surrounded by outer space whose temperature of air be maintained scheduled value with time. Through the various experiments with several parameters, such as flow rate, inlet and outlet temperatures of hot water and the heating duration and so on, we found that the floor heating system with heat pipes was able to reduce
    the pumping power for hot water circulation by 4~31% compared with the conventional panel heating system using PE~X pipe. These results could be used for optimal design and efficient operation of the heating system as well as improvement of thennal comfort.

    keyword Heat pipe(히트파이프), Cross-linked polyethylene(PE-X) pipe(가교화 폴리에틸렌관), Heating characteristic(난방특성),Radiant heating panel(복사난방패널), Thermal comfort(온열 쾌적도)
    저널명 설비공학 논문집 ▷관련저널보기
    VOL 24
    PAGE 183-189